Emergency Gas Shut-Off Valves : Safety Gas Shut Off Valves


Chlorine gas is still the most effective and efficient means to disinfect!

GA-170 Gas Detector Global Treat, Inc. provides the industry's finest chemical gas feeders in addition to high quality safety control monitors such as the GA-170 Gas Detector together with the very reliable Robo Control automatic shut off valve.

Use of emergency shut off valve systems can greatly reduce the risk of a significant gas release. The system will close the gas cylinder valves(s) within seconds of activating a manual panic button, an external alarm signal, or an internal fail-safe alarm signal.

*Product conforms to CHLORINE INSTITUTE publication recommendations on emergency closure devices for container valves.



More information for Chlorine Shut Valve Actuators/Emergency Shut Off Valve Systems & Fire Codes can be found at the bottom of this page.

  • Can be used on chlorine and sulfur dioxide 150# cylinders or ton containers
  • Battery operated with automatic charger
  • 120/240 VAC Charger
  • Nema 4X Enclosure
  • Three digit LED display
  • Three inputs maximum
  • Four outputs maximum
  • Remote control by leak detector, panic button, or digital signal such as PLC, or computer



Global Treat, Inc.
Phone: 1.800.370.4410
Fax: 281.370.3571
Contact Support for: Water Treatment Solutions

For distributorship information, click here



Wastewater Treatment | Chlorine Analyzer | Gas Feed Chlorinators | Chemical Liquid Feed System | Automatic Valves : Gas Liquid | Solid Tablet Feeder Systems | Turn Key Systems | Miscellaneous Chlorination Services | Chemical Induction Pumps | Gas Detectors | Gas Shut Off Valves | Vacuum Gas Liquid Monitors | Wastewater Plants | Industrial Scales | Fiberglass Buildings | Chlorine Test Kits & Accessories | New Chlorination Products

© Global Treat, Inc.



Note: The reader is urged to obtain a copy of the current IFC and UFC codes to ensure the exact wording and to assist in proper system design.

FIRE CODES:
Two current( 2003) model codes still require enclosed systems and scrubbers as a containment method. Exceptions that allowed the use of CI Emergency Kits are still allowable. However, the two 2003 Fire Code models have undergone new revisions that are as follows:

IFC -
The 2003 IFC provides an exception to the use of containment systems when gas detectors and automatic valve operators (shut off systems) are provided. The following is an abstract from the current IFC 2003 statements regarding the use of automatic valve closing devices:

From Treatment Systems - 3704.2.2.7 - exceptions to the requirement for a scrubber are allowed in storage or use areas for toxic and highly toxic gases where (there is):

  a) A gas detection system with a sensing interval not exceeding 5 minutes.
  b) An approved automatic-closing fail-safe located immediately adjacent to cylinder valves.
  c) Treatment systems are not required for toxic gases supplied by portable tanks not exceeding       660 gallons. (Equivalent to 6600 lbs.)

Comments: The 2003 IFC allows the storage and use of 150 pound cylinders and ton containers without the requirement of scrubbers or other containment systems when an automatic, fail-safe shut off valve is employed in the facility at the tank valve.

Note: The reader is urged to obtain a copy of the current IFC code. » www.iccsafe.org

UFC -
The 2003 UFC allows the use of toxic or highly toxic gases where treatment systems (scrubbers) or containment systems are provided. However, an exception to the use of these systems when gas detectors and automatic shut off valves are provided. The following is an abstract from the current UFC 2003 statements regarding the use of automatic valve closing devices:

From Treatment Systems - 63.3.8.3.2 - exceptions are provided when (there is):

  a) A gas detection system with a sensing interval not exceeding 5 minutes.
  b) An approved automatic-closing fail-safe located immediately adjacent to active container,       cylinder or tank valves.
  c) There is no limit neither provided nor mentioned about the size of the gas container.

Comments: The 2003 UFC allows the storage and use of 150 pound cylinders and ton containers without the requirement of scrubbers or other containment systems when an automatic, fail-safe shut off valve is employed in the facility at the tank valve.

Note: The reader is urged to obtain a copy of the current UFC code. » www.nfpacatalog.org




Please note that his web page will include search references to: the Powell chlorine emergency shut off valve closure system, a halogen chlorine valve actuator system, Halogen chlorine actuators, Powell chlorine actuators, and the ever so popular Robo Control chlorine actuators.